YF type spring operating mechanism (incoming mechanism) is suitable for XGN -12/T630-25 and XGN -12/T1250-31.5 indoor high voltage SF6 load switch, It's rated voltage is 12KV. This series of mechanisms is made
according to the principle of spring over-discharge. There are three working positions: closing, opening and earthing. It has moderate volume and strong adaptability with convenience. It has the function of tipping the fuse
and adding shunt tripping coil and overload current tripping coil.
The institution meets related requirements of GB3804-2004 "3.6KV-40.5KV high voltage AC load switch", GB16926-1997 "AC high voltage load switch-fuse-combination unit"
Operating specification
O Closing operation of load switch
The mechanism is fixed to the body and inserted into the closing operation shaft (below side) using a dedicated operating handle. Rotating
the mechanism drives the contact to quickly perform the closing action of the load switch. The electric operation motor is energized to drive the
mechanism to complete the switch-closing operation
O Opening operation of load switch
Using a dedicated operating handle to insert into the closing operation shaft (below side), rotate counterclockwise to open, the mechanism
drives the spindle to complete the quick opening action
O Earthing closing operation of load switch
The operating handle is inserted into the earthing shaft (top side) to turn 90 degrees counterclockwise, and the earthing circuit is closed by
the body under the action of the spring force of the mechanism
O Earthing opening operation of load switch
The operating handle is turned about 90 degrees counterclockwise, and the earthing circuit is opened by the body under the action of the spring force of the mechanism
Note : 1.Please specify the voltage level when you order the electric spring mechanism, such as DC220、 DC110、 DC48、 DC24 etc
2.lf the user needs to shunt trip coil please specify the voltage level when ordering.lf not indicated, it's the same as the electric operating motor voltage level